Flotronics Vacuum Condensate Systems
Venturi Systems vs. Positive Displacement Type Vacuum Producers
| (*) CFM @ 5-1/2" hg. | Venturi Type HP Req'd | Flotronics Lobe Type HP Req'd |
FLOTRONICS SAVINGS |
| 23 | 5 | 1 | 4 |
| 30 | 7-1/2 | 1-1/2 | 6 |
| 75 | 10 | 3 | 7 |
| 130 | 15 | 5 | 10 |
| 160 | N.A. | 7-1/2 | Super Efficient |
| 225 | N.A. | 7-1/2 | Super Efficient |
Air Removal Recommendations
| Standard Systems | 1.5 CFM Per 1000 EDR |
| Replacing Steam Pumps | 2.5 CFM Per 1000 EDR |
Sq. Feet EDR / 4 = Lbs./Hr